Selecting the appropriate battery pack configuration is fundamental to designing or choosing an energy storage system. For applications ranging from DIY power banks to high-voltage kommersielle energilagringssystemer (ESS), understanding terms such as 8S2P, 16S2P, eller 96S2P directly impacts performance, cost, safety, and system compatibility.
This document details these configurations, clarifies series and parallel cell connections, and provides guidance for selecting the optimal battery pack setup for specific applications.
What Do 4S1P, 8S2P, 16S2P, and 96S2P Mean?
The notation XSYP describes how cells are connected:
- S (Series): Cells connected end-to-end, increasing total spenning
- P (Parallel): Cells connected side-by-side, increasing total kapasitet
Configuration | Cells (Series × Parallel) | Total Cells | Typical Voltage | Typical Capacity |
---|---|---|---|---|
4S1P | 4 × 1 | 4 | 12.8V | 1× cell capacity |
8S2P | 8 × 2 | 16 | 25.6V | 2× cell capacity |
16S2P | 16 × 2 | 32 | 51.2V | 2× cell capacity |
96S2P | 96 × 2 | 192 | 307.2V | 2× cell capacity |
Typiske bruksområder
- 4S1P: Small 12 V litiumbatteri like RVs, trolling motors, or basic solar kits
- 8S2P: Medium-sized 24V solar storage or backup power systems
- 16S2P: High-capacity 48V solar setups and commercial ESS
- 96S2P: High-voltage electric vehicles (EVs), industrial backup, and grid storage
Series vs. Parallel Connections Explained
What Is Series (S)?
Connecting cells in serie adds their voltages while the capacity remains the same.
- Eksempel: Single LiFePO4 cell = 3.2V, 100Ah 4S pack voltage = 4 × 3.2V = 12.8V, capacity = 100Ah 16S pack voltage = 16 × 3.2V = 51.2V, capacity = 100Ah
Use case: When your system requires higher voltage (e.g., powering inverters or motors).
What Is Parallel (P)?
Connecting cells in parallell adds capacity while the voltage stays constant.
- Eksempel: Single cell = 3.2V, 100Ah 2P pack capacity = 2 × 100Ah = 200Ah, voltage = 3.2V
Use case: When you want longer runtime or increased energy storage.
Calculating Voltage, Capacity, and Energy
Parameter | Example (16S2P LiFePO4, 100Ah cells) |
---|---|
Total Voltage = Cell V × S | 3.2V × 16 = 51.2V |
Total Capacity = Cell Ah × P | 100Ah × 2 = 200Ah |
Total Energy = V × Ah / 1000 | 51.2V × 200Ah = 10.24 kWh |
Real-World Battery Pack Examples
Søknad | Configuration | Spenning | Kapasitet | Merknader |
---|---|---|---|---|
Bobilbatteri | 4S2P | 12.8V | 200Ah | Perfect for 12V DC systems |
Home ESS | 16S1P | 51.2V | 100Ah | Standard 48V system |
Golfvogn | 8S3P | 25.6V | 300Ah | Suited for 24V systems |
Industrial ESS | 96S2P | 307.2V | 200Ah | High voltage, high energy |
Series vs. Parallel: Which Should You Choose?
Series (Higher Voltage)
Fordeler:
- Delivers higher voltage for powerful loads
- Lower current reduces wiring gauge and energy loss
- Compatible with standard inverter voltage inputs
Disadvantages:
- Requires precise BMS balancing to prevent cell mismatch
- A single cell failure can impact the whole pack
Parallel (Higher Capacity)
Fordeler:
- Increases runtime and overall energy storage
- Easier to replace individual cells
- Suitable for low voltage, high capacity needs
Disadvantages:
- Higher current requires thicker cables and better cooling
- Risk of current imbalance due to uneven aging
Summary Comparison
Funksjon | Serie | Parallell |
---|---|---|
Increases | Spenning | Kapasitet |
Strømtrekk | Lavere | Høyere |
Typisk bruk | Motors, inverters | Backup power, long runtime |
Main Challenge | Voltage balancing | Current balancing |
Safety note: Improper series-parallel mixing can cause cell imbalance, thermal runaway, and BMS faults. Always consult experts when designing battery packs.
Configurations for LiFePO4 and Sodium-ion Cells
Søknad | Recommended Setup | Spenning | Kapasitet |
---|---|---|---|
Bobilbatteri | 4S2P | 12.8V | 200Ah |
Marinebatteri | 8S1P | 25.6V | 100Ah |
Golfbilbatteri | 8S3P | 25.6V | 300Ah |
Energilagring i hjemmet | 4S / 8S / 16S | 12.8V / 25.6V / 51.2V | Varied |
Sodium-ion vs. LiFePO4 Voltage Comparison
- Natrium-ion-batteri nominal voltage: ~2.8V per cell
- LiFePO4 nominal voltage: ~3.2V per cell
Target Voltage | Sodium-ion (2.8V) | LiFePO4 (3.2V) |
---|---|---|
48V | 18S | 16S |
12V | 5S | 4S |
Impact of Configuration on Performance, Cost & Safety
- More Series Cells: Higher voltage but requires complex BMS, insulation, and safety protocols
- More Parallel Cells: Increases capacity but challenges current balancing and thermal management
- Design Considerations: Series reduces wiring bulk but demands better insulation; parallel needs thicker cables and enhanced cooling
- Compatibility: Battery pack voltage and current must match inverter and load specs for efficiency and safety
Matching Battery Packs to Inverter Voltage
Inverter Voltage | Recommended Configuration |
---|---|
12V | 4S |
24V | 8S |
48V | 16S |
300V+ | 96S+ |
How to Choose the Right Battery Configuration: 5 Key Questions Answered
Choosing the correct battery configuration is essential for performance, safety, and compatibility with your system. Here are the top 5 questions you must answer before deciding.
choose the best battery configuration:
- Match voltage (S) to your inverter
- Størrelse capacity (P) to your runtime and load
- Balance space, weight, and safety
- Confirm full compatibility with your BMS and inverter
For høyspenningsbatteri or custom energy storage systems (e.g., 96S2P, 48S3P), work with a professional lithium battery manufacturer who can customize the solution to your exact specs.
1. What system voltage does your application require?
You should choose the number of cells in series (S) based on your required system voltage.
For example:
- A 48V system typically uses 16 LiFePO4 cells in series (16S), each at 3.2V, totaling 51.2V.
- For 24V systems, use 8S (25.6V).
- Industrial systems may require high-voltage configurations like 96S for 307.2V.
Tip: Always check the inverter’s rated input voltage to match your battery pack correctly.
2. How much battery capacity do you need?
Capacity (Ah) determines how long your battery can power your load and is increased through parallel (P) connections.
For instance:
- 1P = 100Ah
- 2P = 200Ah (two cells connected in parallel)
- 3P = 300Ah
Use parallel cells to extend runtime or meet high-current demands.
Tip: Calculate your energy needs using: Voltage × Capacity = Total Energy (Wh).
3. What is your load’s current draw (continuous and peak)?
If your system draws high continuous or peak current, you need more parallel cells to safely distribute the load.
Each cell has a maximum discharge rate. Too much load on too few cells may cause overheating or system failure. A 2P or 3P configuration helps handle larger loads without stressing the cells.
Tip: Check both inverter surge current and motor startup current when sizing.
4. Do you have space or weight limitations?
Yes—your available space may restrict how many cells you can use in parallel or series.
- More parallel cells = more capacity but also more weight and space.
- More series cells = higher voltage without increasing physical size as much.
In RVs, golf carts, or marine settings, compact design often matters more than large capacity.
Tip: Ask your battery manufacturer for modular or stackable pack designs.
5. What are the specifications of your inverter and BMS?
Always match your battery configuration to your inverter and battery management system (BMS).
Key specs to verify:
- Inverter input voltage range
- Max continuous and peak current
- BMS supported voltage range and cell count
A mismatch can lead to poor performance, error codes, or even system damage.
Tip: Provide your inverter datasheet to the battery supplier for proper pack design.
Konklusjon
Choosing the right battery pack configuration balances voltage, capacity, safety, and cost. Series connections increase voltage for powerful loads, while parallel connections extend runtime and energy storage. Proper design and expert advice are critical for optimal, safe, and reliable battery systems.
Need expert help designing or customizing your lithium or sodium-ion battery pack? Kontakt Kamada Power technical team for tailored OEM solutions and professional guidance.
VANLIGE SPØRSMÅL
1. What does 8S2P mean in a battery pack?
8S2P means the battery pack has 8 cells connected in series and 2 sets in parallel. In this configuration, the voltage equals the sum of 8 cells, and the capacity is doubled. For example, using LiFePO4 cells (3.2V, 100Ah), 8S2P provides 25.6V and 200Ah, making it suitable for 24V systems such as golf carts, marine batteries, and small solar storage.
2. What is the difference between 8S2P, 16S2P, and 96S2P battery packs?
The main difference lies in voltage level and energy capacity.
- 8S2P = 25.6V, 200Ah
- 16S2P = 51.2V, 200Ah
- 96S2P = 307.2V, 200Ah
More series cells increase spenning, while parallel cells increase kapasitet. Choose based on your inverter voltage and power requirements. 96S2P is common in high-voltage EV or industrial energy storage systems.
3. Should I connect batteries in series or parallel?
Connect in series if you need higher voltage; connect in parallel if you need higher capacity.
- Series (S): Adds voltage (e.g., for 48V inverter systems)
- Parallel (P): Adds capacity (longer runtime, more amp-hours)
In practice, most systems use a combination of both to meet energy and voltage needs. Always ensure proper BMS (battery management system) support.
4. How do I calculate the voltage and capacity of a battery pack?
Multiply the number of series cells by cell voltage for total voltage; multiply parallel cells by cell capacity for total capacity.
Formel:
- Voltage = Series cells × Cell voltage
- Capacity = Parallel cells × Cell Ah
- Energy = Voltage × Capacity ÷ 1000 (in kWh)
Eksempel: A 16S2P battery using 3.2V, 100Ah cells =
- 51.2V (16 × 3.2V)
- 200Ah (2 × 100Ah)
- 10.24 kWh (51.2V × 200Ah ÷ 1000)
5. What battery configuration is best for a 48V inverter?
Use a 16S configuration with LiFePO4 batteries to match 48V inverters. Each LiFePO4 cell is 3.2V, so 16 cells in series provide 51.2V, which is optimal for 48V inverter inputs. This is the standard in most solar and home energy storage systems.
6. Can I mix series and parallel connections in one battery pack?
Yes, combining series and parallel connections is common in battery packs. Example: 16S2P means two sets of 16 cells connected in series, then paralleled. However, mixing must be carefully balanced with a proper BMS to avoid overheating, imbalance, and safety risks.
7. Is 96S2P suitable for home energy storage?
No, 96S2P is too high-voltage for typical home ESS. With a nominal voltage of over 300V, it’s designed for industrial energy storage, grid-scale applications, and electric vehicles. Home ESS systems usually use 16S (51.2V) or 8S (25.6V) configurations for safety and inverter compatibility.
8. How do I match battery packs to inverter voltage?
Match battery voltage output closely to your inverter’s rated input. Here’s a quick guide:
Inverter Voltage | Recommended Battery Setup |
---|---|
12V | 4S (12.8V) |
24V | 8S (25.6V) |
48V | 16S (51.2V) |
300V+ | 96S (307.2V) |
Always verify with your inverter specs before finalizing the battery pack configuration.
9. What type of BMS do I need for 96S2P battery pack?
You need a high-voltage BMS rated for at least 96 series cells, with balancing and protection up to 307.2V. These BMS units are usually custom-designed for industrial ESS or electric vehicle platforms. Ensure the BMS supports:
- Voltage and thermal protection
- Active/passive balancing
- CAN/RS485 communication
- Fault reporting
10. Can LiFePO4 and sodium-ion batteries use the same configuration?
No, natrium-ion-batteri and LiFePO4 cells have different nominal voltages, so series count differs.
Batteritype | Nominell spenning | 48V System Configuration |
---|---|---|
LiFePO4 | 3.2V | 16S |
Sodium-ion | 2.8V | 18S |
Always confirm with your BMS and inverter compatibility before using sodium-ion cells.